Circular sizing selects the next standard diameter up. Rectangular sizing rounds width and height up to the nearest 50 mm.

Result

Duct Size
-
Enter values and click calculate.

Method

Required duct area is determined from airflow and design velocity:

A = Q ÷ v

For circular ducts:

d = √(4A ÷ π)

For rectangular ducts:

A = W × H

Velocity pressure may be estimated from:

Pᵥ = 0.5 × ρ × v²
  • A = duct area (m²)
  • Q = airflow rate (m³/s)
  • v = air velocity (m/s)
  • d = circular duct diameter (m)
  • W = rectangular duct width (m)
  • H = rectangular duct height (m)
  • Pᵥ = velocity pressure (Pa)
  • Calculated result = -

Reference

  • An air density of 1.2 kg/m³ is assumed for velocity pressure checks.
  • Duct sizing is commonly undertaken using guidance contained within CIBSE Guide B2, CIBSE Guide C and methods presented in CIBSE Guide C4.
  • The velocity presets in this calculator represent indicative design conventions only, used in practice to balance duct size, noise and pressure drop.
  • Where applicable, final design should align with Approved Document F, project specifications, ductwork standards and manufacturer requirements.
Design note: This calculator provides an indicative duct size or velocity check only. Final design should consider noise criteria, pressure drop, space constraints, fan selection, duct classification, leakage and project-specific requirements.